top of page
FS7 Flame Detector

FS7 Flame Detector

£0.00Price

The FS7 Flame Detector provides and intelligent two-stage response to semiconductor wet bench fires:

Stage 1: Alert. This is the first-stage response to a small fire with a heat energy output of 3 kW (the equivalent of a 4-inch diameter polypropylene pool fire). This allows time for the fire to self-extinguish.

Stage 2: Alarm. If the fire does not self-extinguish, and grows to the Factory Mutual specified heat energy threshold of 13 kW (the equivalent of an 8-inch diameter polypropylene pool fire), the second-stage response is activated.

 

The FS7-2173 is used with the FS7-130-SX Controller or Control Panel FSWB. Controller and Control Panel supply power to detectors monitor the status of all detectors and communicate with the detectors via the digital RS-485 communication channel. FS7-2173 is supplied with a standard 20 ft. cable connector. Detectors are connected to the controller or control panel using the self-locking connectors and junction boxes. This allows for fast and easy connections eliminating wiring problems. Each detector can store up to six time and date stamped FirePics™ (pre-event multi-spectral sensor array data) in non-volatile memory. Controller and control panel can also store event history table in the non-volatile memory, which contains the time and date stamped alert, alarm and fault histories. FirePics™ and event histories can be retrieved from the controller or control panel.

 

The FS7-2173-2RP unitized model’s microprocessor, with digital signal processing algorithms, continuously monitors the circuitry, sensor’s built-in self-test and verifies proper operation. FS7-2173-2RP with discrete relay outputs is designed to operate as a stand-alone detector and interface with any approved fire alarm panel. The detector requires an external 24 VDC power source and is supplied with a standard 20 ft. pigtail cable. It can store up to six time and date stamped FirePics™ and 200 events in non-volatile memory. FirePics™ and event histories can be retrieved using a FS7 Interface Kit and the Windows-based PC software.

 

Additional Features and Benefits

  • Multi-Spectral digital electro-optical radiant energy infrared fire detector
  • Unique two-stage fire detection response
  • Immune to false alarm sources
  • NOT affected by absorbing smoke, gasses or chemical vapors
  • NOT sensitive to background radiant energy from electric heaters and ovens
  • Detects hydrocarbon and non-hydrocarbon fires
  • Rugged leak-proof, heat-sealed, acid-resistant, injection-molded polypropylene housing
  • Wide 120° field-of-view
  • Digital communication with RS-485 interface
  • FirePic™; time and date-stamped digital fire signatures
  • Built-in detector automatic self test
  • Unitzed model design for stand-alone operation
  • Product Info

    Multi-spectral WideBand IR™, Near Band IR and Visible Band flame detectors are designed specifically for semiconductor Clean Room fire protection applications.

     

    Features & Benefits

    • Unique two-stage fire detection response
    • Immune to false alarm sources
    • Detects hydrocarbon and non-hydrocarbon fires

     

    Quick Specs

    • Field of view: 120° horizontal and vertical
    • Operating Voltage: 24 VDC nominal (18-28 VDC) - regulated
    • Operating temperature range: 32° to +158°F (0 to 70°C)
  • Downloads

  • Delivery

    We aim to Delivery products with you within 4 weeks of receipt of order. However, in exceptional circumstances delivery may be up to 6 weeks due to manufacturer lead times. Please inform us if you require fast delivery as we will do our utmost to expedite your order.

  • Quantity Orders

    Please contact us directly to discuss quantity purchases and additional discounts.  We will subsequently provide you with a formal quote with the applied discount, which will be valid for 30 days 

  • Hire

    Many of the products you have seen are available for hire, so feel free to contact us if you would prefer to hire this instrument.

bottom of page