FS7 Flame Detector
The FS7 Flame Detector provides and intelligent two-stage response to semiconductor wet bench fires:
Stage 1: Alert. This is the first-stage response to a small fire with a heat energy output of 3 kW (the equivalent of a 4-inch diameter polypropylene pool fire). This allows time for the fire to self-extinguish.
Stage 2: Alarm. If the fire does not self-extinguish, and grows to the Factory Mutual specified heat energy threshold of 13 kW (the equivalent of an 8-inch diameter polypropylene pool fire), the second-stage response is activated.
The FS7-2173 is used with the FS7-130-SX Controller or Control Panel FSWB. Controller and Control Panel supply power to detectors monitor the status of all detectors and communicate with the detectors via the digital RS-485 communication channel. FS7-2173 is supplied with a standard 20 ft. cable connector. Detectors are connected to the controller or control panel using the self-locking connectors and junction boxes. This allows for fast and easy connections eliminating wiring problems. Each detector can store up to six time and date stamped FirePics™ (pre-event multi-spectral sensor array data) in non-volatile memory. Controller and control panel can also store event history table in the non-volatile memory, which contains the time and date stamped alert, alarm and fault histories. FirePics™ and event histories can be retrieved from the controller or control panel.
The FS7-2173-2RP unitized model’s microprocessor, with digital signal processing algorithms, continuously monitors the circuitry, sensor’s built-in self-test and verifies proper operation. FS7-2173-2RP with discrete relay outputs is designed to operate as a stand-alone detector and interface with any approved fire alarm panel. The detector requires an external 24 VDC power source and is supplied with a standard 20 ft. pigtail cable. It can store up to six time and date stamped FirePics™ and 200 events in non-volatile memory. FirePics™ and event histories can be retrieved using a FS7 Interface Kit and the Windows-based PC software.
Additional Features and Benefits
- Multi-Spectral digital electro-optical radiant energy infrared fire detector
- Unique two-stage fire detection response
- Immune to false alarm sources
- NOT affected by absorbing smoke, gasses or chemical vapors
- NOT sensitive to background radiant energy from electric heaters and ovens
- Detects hydrocarbon and non-hydrocarbon fires
- Rugged leak-proof, heat-sealed, acid-resistant, injection-molded polypropylene housing
- Wide 120° field-of-view
- Digital communication with RS-485 interface
- FirePic™; time and date-stamped digital fire signatures
- Built-in detector automatic self test
- Unitzed model design for stand-alone operation
Product Info
Multi-spectral WideBand IR™, Near Band IR and Visible Band flame detectors are designed specifically for semiconductor Clean Room fire protection applications.
Features & Benefits
- Unique two-stage fire detection response
- Immune to false alarm sources
- Detects hydrocarbon and non-hydrocarbon fires
Quick Specs
- Field of view: 120° horizontal and vertical
- Operating Voltage: 24 VDC nominal (18-28 VDC) - regulated
- Operating temperature range: 32° to +158°F (0 to 70°C)
Downloads
Delivery
We aim to Delivery products with you within 4 weeks of receipt of order. However, in exceptional circumstances delivery may be up to 6 weeks due to manufacturer lead times. Please inform us if you require fast delivery as we will do our utmost to expedite your order.
Quantity Orders
Please contact us directly to discuss quantity purchases and additional discounts. We will subsequently provide you with a formal quote with the applied discount, which will be valid for 30 days
Hire
Many of the products you have seen are available for hire, so feel free to contact us if you would prefer to hire this instrument.